Appliance Tester BENNING ST 720
Mains-operated and battery-operated Appliance Tester for mobile testing of electrical devices
- testing in compliance with DIN VDE 0701-0702 (EN 62638), BGV A3, BetrSichV (German Health and Safety at Work Regulations), ÖVE/ÖNORM E 8701, NEN 3140
- quick - testing within a few seconds
- all-in-one - appliance tester and RCD tester in one single device
- unique - testing of single-phase and three-phase devices under operating conditions
Testing of devices with mains voltage-dependent switching elements/mains-supply units/relays such as controlled devices/tools, devices of information and communication technology as well as of devices which can be tested completely with mains voltage only.
In mains operating mode, the protective conductor current/contact current is measured by means of the required differential current/direct measurement method.
Features BENNING ST 720
- mains operating mode for tests under operating conditions
- battery operating mode for mobile testing
- automatic testing procedure for devices of class I (key 1), class II/III (key 2) and line test (key 1)
- reduction of the ISO testing voltage for devices with overvoltage arresters
- testing of RCDs with 30 mA
- indication of correct function key in case of incorrect operation, overload and if the test sample is not switched on
- sufficient battery capacity for more than 2,500 test samples
- limiting values preset in compliance with DIN VDE standard
- measuring result with “pass/fail” information
Measuring functions
- protective conductor resistance with a testing current of 200 mADC
- insulating resistance with a testing voltage of 250 V/500 VDC
- mains operating mode: protective conductor current/contact current by means of differential current/direct measurement method with automatic mains pole reversal
- battery operating mode: protective conductor current/contact current by means of alternative leakage current measurement method
- tripping time measurement of RCDs with 30 mA
- voltage measurement on external shock-proof socket
- active testing of three-phase devices under operating conditions by means of optional measuring adapters (item no. 044140/044141)
| BENNING ST 720 |
indication | graphic display |
protective conductor resistance | 0,05 Ω - 20 Ω |
testing current | ± 200 mADC |
insulation resistance | 0,1 MΩ - 20 MΩ |
testing voltage | 250 V / 500 VDC |
protective conductor current/ contact current by means of | |
-differential current measurement | 0,25 mA - 20 mA |
-alternative leakage current measurement | 0,25 mA - 20 mA |
-direct measurement | 0,1 mA - 2 mA |
testing current of RCD | 30 mA |
tripping time | 10 ms - 500 ms |
protective conductor current of three-phase test objects under operating conditions (optional) | 0,25 mA - 10 mA |
line test | RPE, RISO, short-circuit test and continuity, test of phase conductor (L) and neutral conductor (N) |
voltage measurement on external shock-proof socket | 50 V - 270 V (L-N, L-PE, N-PE) |
scope of delivery | carrying case, test cable with alligator clip, mains connection cable, appliance cable, battery set |
item no. | 050312 |
overview catalogue (english) | |
brochure (german) | |
instruction manual | |
test certificates (Excel) | |
test certificates (PDF) |
Subject to technical changes!