Safety Instrument BENNING IT 120 B

3D Model

Installation tester for complete safety tests on electrical systems including all-current-sided FI/RCD circuid breaker type B according to DIN VDE 0100 and IEC 60364

  • measurement of the protective conductor line and of the equipotential bonding line with a testing current of 200 mA
  • measurement of the insulation resistance with testing voltages of 100 V, 250 V, 500 V and 1000 V
  • line impedance and loop impedance measurement (optional without tripping of the RCD) with calculation of the shortcircuit current (PFC/ PSC)
  • complete testing of the residual-current-operated device (RCD)
  • measurement of contact voltage (without tripping), tripping time and tripping current of residual current operated device (RCD)
  • phase-sequence testing in three-phase mains
  • voltage measurement up to 500 V and online voltage monitoring
  • all measuring functions can be selected directly by means of a rotary switch
  • switchable probe tip for releasing the measuring process
  • graphic display and help function with connecting diagram
  • complete measuring result with measuring parameters, limiting value and symbols for PASS / FAIL
  • current supply by means of 6 NiMH storage batteries (AA) with charger
  • earthing measurement by means of three-wire measuring method (optionally with earthing set)
  • current measurement (TRUE RMS) by means of current clamp adapter (optional)
  • illumination measurement by means of lux sensor (optional)
  • integrated measured value memory for 500 measurements
  • USB and RS 232 interface
  • BENNING PC-Win IT 120 B software included in delivery

 

Information:
RCDs of the type B are increasingly used for multi-phase equipment of power electronics. In case of a fault, these devices also detect smooth DC fault currents and high-frequency AC fault currents.

 

BENNING IT 120 B 

display

graphic display (illuminated)

low-impedance resistance

0,01 Ω - 2.000 Ω

insulation resistance

1 kΩ - 1.000 MΩ

line impedance (L-N/L)

0,01 Ω - 2.000 Ω

loop impedance (L-PE)

0,01 Ω - 2.000 Ω

short-circuit current

0,01 A - 24,4 kA

RCD testing

tripping time, tripping current, contact voltage

phase sequence

yes

voltage, frequency

1 V - 500 V, 45 Hz - 65 Hz

earth resistance

0.01 Ω - 2000 Ω (by means of earthing set)

current (TRUE RMS)

0.1 mA - 20 A (by means of the clamp)

luminous intensity

0.01 lux - 20 klux (by means of sensor)

measured value memory

500 measuring results

interfaces

USB, RS 232

incl. software

BENNING PC-Win IT 120 B

item no.

044102

productoverview
(english)

Download

instruction manual

Download

brochure
(german)

Download

 

Technical changes, model or color modifications, mistakes and delivery facilities without notice! No responsibility for literal mistakes.

» Download further brochures in other languages