Appliance Tester BENNING ST 720

Mains-operated and battery-operated Appliance Tester for mobile testing of electrical devices

  •  testing in compliance with DIN VDE 0701-0702 (EN 62638), BGV A3, BetrSichV (German Health and Safety at Work Regulations), ÖVE/ÖNORM E 8701, NEN 3140
  • quick - testing within a few seconds
  • all-in-one - appliance tester and RCD tester in one single device
  • unique - testing of single-phase and three-phase devices under operating conditions

Testing of devices with mains voltage-dependent switching elements/mains-supply units/relays such as controlled devices/tools, devices of information and communication technology as well as of devices which can be tested completely with mains voltage only.

In mains operating mode, the protective conductor current/contact current is measured by means of the required differential current/direct measurement method.

Features BENNING ST 720

  • mains operating mode for tests under operating conditions
  • battery operating mode for mobile testing
  • automatic testing procedure for devices of class I (key 1), class II/III (key 2) and line test (key 1)
  • reduction of the ISO testing voltage for devices with overvoltage arresters
  • testing of RCDs with 30 mA
  • indication of correct function key in case of incorrect operation, overload and if the test sample is not switched on
  • sufficient battery capacity for more than 2,500 test samples
  • limiting values preset in compliance with DIN VDE standard
  • measuring result with “pass/fail” information

Measuring functions

  • protective conductor resistance with a testing current of 200 mADC
  • insulating resistance with a testing voltage of 250 V/500 VDC
  • mains operating mode: protective conductor current/contact current by means of differential current/direct measurement method with automatic mains pole reversal
  • battery operating mode: protective conductor current/contact current by means of alternative leakage current measurement method
  • tripping time measurement of RCDs with 30 mA
  • voltage measurement on external shock-proof socket
  • active testing of three-phase devices under operating conditions by means of optional measuring adapters (item no. 044140/044141)




BENNING ST 720

indication

graphic display

protective conductor resistance

0,05 Ω - 20 Ω

testing current

± 200 mADC

insulation resistance

0,1 MΩ - 20 MΩ

testing voltage

250 V / 500 VDC

protective conductor current/ contact current by means of

-differential current measurement

0,25 mA - 20 mA

-alternative leakage current measurement

0,25 mA - 20 mA

-direct measurement

0,1 mA - 2 mA

testing current of RCD

30 mA

tripping time

10 ms - 500 ms

protective conductor current of three-phase test objects under operating conditions (optional)

0,25 mA - 10 mA

line test

RPE, RISO, short-circuit test and continuity, test of phase conductor (L) and neutral conductor (N)

voltage measurement on external shock-proof socket

50 V - 270 V (L-N, L-PE, N-PE)

scope of delivery

carrying case, test cable with alligator clip, mains connection cable, appliance cable, battery set

item no.

050312

overview catalogue (english)

Download

brochure (german)

Download

instruction manual

Download

test certificates (Excel)

Download

test certificates (PDF)

Download

Subject to technical changes!

» Download further documents (e.g. catalogues, instruction manuals)